Electrical Requirements
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine
that the ground path and the wire gauge are in accordance
with local codes.
Check with a qualified electrical installer if you are not
sure the oven is properly grounded.
This oven must be connected to a grounded metal, permanent
wiring system.
Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition or CSA Standards C22.1-94, Canadian
Electrical Code, Part 1 and C22.2 No. O-M91-latest edition,
and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
Electrical Connection
To properly install your oven, you must determine the type
of electrical connection you will be using and follow the
instructions provided for it here.
Oven must be connected to the proper electrical voltage and
frequency as specified on the model/serial/rating plate. The
model/serial/rating plate is located under the control panel on
single ovens and under the control panel on the upper oven
cavity on double ovens. See the following illustrations.
Models rated from 7.3 to 9.6 kW at 240 volts (5.4 to 7.4 kW
at 208 volts) require a separate 40-amp circuit. Models
rated at 4.8 kW and below at 240 volts (3.6 kW and
below at 208 volts) require a separate 20-amp circuit.
A circuit breaker is recommended.
Connect directly to the circuit breaker box (or fused
disconnect) through flexible, armored or nonmetallic
sheathed, copper cable (with grounding wire). See
“Make Electrical Connection” section.
Flexible conduit from the oven should be connected
directly to the junction box.
Fuse both sides of the line.
Do not cut the conduit. The length of conduit provided
is for serviceability of the oven.
A UL listed or CSA approved conduit connector must
be provided.
If the house has aluminum wiring, follow the
procedure below:
1. Connect a section of solid copper wire to the ends
of the flexible conduit leads.
2. Connect the aluminum wiring to the added section
of copper wire using special connectors and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended
procedure. Aluminum/copper connection must conform
with local codes and industry accepted wiring practices.
For power requirements for models JJW2430D, JJW2427D,
JJW2830D, JJW2827D, JJW2730D, JJW2727D, JJW3430D
and JJW3820D, refer to the following table.
Single Oven
A. Model/serial/rating plate
Double Oven
A. Model/serial/rating plate
A
A
240 VAC 208 VAC
Model Watts Amps Watts Amps
JJW2430D
JJW2427D
4141 17.8 3145 15.6
JJW3430 4193 18.3 3193 16.1
JJW2830D
JJW2827D
8279 35.7 6288 31.2
JJW3820D 8363 36.6 6386 32.1
JJW2730D
JJW2727D
8221 34.3 6230 30.7